NRW Intelligence

Network Dashboard

3 Active Alerts
Live — Last updated 06 Jun 2026, 22:48 UTC
NRW Risk Score
+12 pts
78/100

HIGH — Immediate investigation required

Leakage Probability
+7%
83%

Est. 48.2 m³/hr real losses

Burst Risk Score
-8 pts
34/100

MODERATE — Monitor transients

Average Pressure
+0.14
4.82bar

69.9 psi · 482 kPa

Minimum Pressure
-0.22
2.31bar

At 03:47 UTC — PL-047

Maximum Pressure
+0.38
7.14bar

At 07:12 UTC — exceeds 7.0 bar limit

Pressure Stability Index
-9 pts
61/100

FAIR — High diurnal variance

Average Flow
+3.2
127.4L/s

458.6 m³/hr zone demand

Peak Flow
+18.3
284.7L/s

At 07:45 UTC — morning peak

Min. Night Flow
+8.1
64.8L/s

Expected ≤42 L/s — excess 22.8 L/s

Infrastructure Stress
+5 pts
72/100

HIGH — pipe fatigue risk elevated

Network Health Score
-6 pts
52/100

FAIR — Multiple issues detected

Hydraulic Efficiency
-4%
71%

Possible valve restriction on FL-012

Data Quality Score

87/100

GOOD — 14/16 loggers nominal

Anomaly & Alert Feed

AI-generated engineering observations · Last 24 hours

5 Events
CRITICALPL-047
03:47 UTC

Sudden pressure drop detected — PL-047

Pressure fell from 6.28 bar to 2.31 bar in under 4 minutes at 03:47 UTC. Indicative of pipe burst or major valve closure upstream.

Confidence:
91%
View Details
Recommended: Dispatch field crew — investigate Section 4B
CRITICALFL-012
02:14 UTC

Minimum Night Flow exceeds threshold — FL-012

MNF of 64.8 L/s recorded against expected baseline of 42.0 L/s. Excess of 22.8 L/s (~82 m³/hr) indicates significant real losses in DMA Zone 4.

Confidence:
87%
View Details
Recommended: Schedule district leak survey within 48 hours
WARNINGPL-047
07:12 UTC

Pressure transient spike — PL-047

Pressure surged to 7.14 bar at 07:12 UTC, exceeding the 7.0 bar operational limit. Possible pump startup transient or valve slam. Monitor for fatigue.

Confidence:
78%
View Details
Recommended: Check pump startup sequence and PRV-04 setting
WARNINGTL-003
01:22 UTC

Data gap — TL-003 offline for 47 minutes

Tank Level Logger TL-003 stopped transmitting between 01:22 and 02:09 UTC. Data gap of 47 records. Tank filling analysis for this period is unreliable.

Confidence:
100%
View Details
Recommended: Inspect logger battery and comms module
MEDIUMFL-012/FL-019
12:00 UTC

Hydraulic efficiency below threshold — FL-012 to FL-019

Head loss between FL-012 and FL-019 is 2.4 bar over 1.8 km — 38% higher than Hazen-Williams prediction (C=120). Possible partial valve closure or heavy sedimentation.

Confidence:
74%
View Details
Recommended: Inspect isolation valve IV-23 and consider pipe condition assessment

Logger Status

6 online · 2 requiring attention

6 OK2 Issues
PL-047Pressure

Inlet Main — Zone 4

4.82 bar
87%
ONLINE
FL-012Flow

Zone 4 Inlet

127.4 L/s
72%
ONLINE
TL-003Tank Level

Hilltop Reservoir

4.21 m
23%
WARNING
PL-023Pressure

Distribution — Node 7

3.94 bar
91%
ONLINE
FL-019Flow

Zone 4 Outlet

98.7 L/s
68%
ONLINE
PM-001Pump Monitor

Pump Station 3

87% duty
95%
ONLINE
PL-091Pressure

PRV-04 Downstream

NO DATA
12%
FAULT
PL-014Pressure

Zone 4 East Branch

4.61 bar
84%
ONLINE